Back > Sheath Testers > MM G 10
 

Technical Specification: MM G 10


Introduction
The Sheath Tester MMG 10 is mainly designed for voltage testing of cable sheaths made of PE or PVC as well as for the location of sheath faults on shield plastic-insulated cables and the detection of earth-leakage faults in plastic-sheathed cables.

In combination with the Sheath Fault Pre-location
Device MVG 5, sheath faults can be pre-located.

The following measurements can be taken with the
MVG 5:

  • Sheath fault pre- location on shielded medium-high voltage cables
  • Pre-location of line-earth faults on plastic-insulated low-voltage cables

Pin-Pointing is carried out by means of the Line-To-
Earth Fault Locating Device ESG 80-2 by measuring the step voltage.

Due to the excellent burn down effect achieved by the
full-wave rectification, this device is very well suited for converting high-resistance cable faults in low-voltage power cables into low-resistance ones.

Moreover our new Sheath Tester MMG 10 has further special features such as:

  • Continuously adjustable output voltage in
    voltage ranges 1000 V, 5000 V, and 10,000 V
  • Protection against overload by voltage and
    current control
  • Fault location at reduced power to prevent damages to adjacent wires or cables
  • Indication of voltage and current by two analog indicating systems
  • Automatic discharge unit provides for removal
    of residual charge and for earthing the test
    object
  • Clock-controlled operation of the voltage source to prevent the drying-out of faults when
    pinpointing sheath faults
 
   

Input Power: 700VA

Mains Connection:
230 V/ 3 A (45/60) Hz

Max. Output Current:

0.5 A

Max. Output Voltage:
10 kV

DC Outpu
t : 1,000 V / 0.5 A
5,000 V / 0.1 A 10,000 V / 0.05 A

Max. Discharge Capacity:
12µF

Current Control:
switching regulator

Voltage Control:
switching regulator

Temperature Monitoring

Indication of High Output Voltage hazardous to touch

Dimensions:
(H X W X D), 200mm x 360mm x 360mm
(without handles)

Weight: Approx:
9 kg
Operation Temperature: -10°C  to +50°C

Storage Temperature:
-20°C to + 60°C

Accessory Equipment:

  • Earth Fault Locating Device: ESG 80-2

  • Earth Spikes with Measuring Leads: EEB

  • Sheath-Fault Pre-locating Device: MVG 5
    (Pre-Location up to 5 kV)

  • Emergency-Off Switch: NAG 1
    for Stand-Alone Operation
     



Cable Master Inc. 160 Pony Dr. #6A, Newmarket, ON, L3Y 7B6
905-715-7303 | Toll Free: 877-715-7303 | Fax: 905-715-7305 info@cablemasterinc.com