Back > Integrated Fault locating Systems >SWG1750

Technical Specification: Model SWG CI-1750,
SWG CDI-1750
32kV Surge Generator Thumper-Burner-Hipot Combination


The SWG series surge generators are designed with switchable, multi-stage surge capacitors and three(3) voltage ranges. This design offers a substantial advantage over single stage capacitor units by allowing the user to minimize the surge voltage and maximize the surge energy and fault current. The voltage in each range can
be adjusted continuously, and a single pulse release or timed pulse repetition is available. In addition the SWG offers a 32kV Hipot function as well as a powerful burn capability
(up to 320mA). The SWG series can be used for primary fault locating in combination with pinpointing devices. By adding a TDR and a surge pulse coupler the unit can perform Surge
Pulse Prelocating. By adding a power filter (ARMfilter) the unit can perform the Arc Reflection Prelocating.
Both units are particularly qualified for fault locating
on long cables with large cross-sections as well as
on PILC cables and duct-bank systems

 
   

Max. Voltage Output in each range: 
 8/16/32kV

Max. Output Energy in each range:
  Model 1750-CI :
1,750 Joules
  Model 1750-CDI: 3,500 Joules

Individual Pulse or Timed Release:
 6-10 sec.

Max. Burn Current 8/16/32kV:
320/160/80 mA

Surge Capacitance Model 1750-CI:
@ 8/16/32kV

55/14/3.4µF

Surge Capacitance Model 1750-CDI:
@ 8/16/32kV

109/27/6.8µF

Power Requirement:
 120VAC/1.75kVA

Footprint (entire system as seen):
 33" x 33"

Weight w/o cable rack approx:
 
350-400 lbs.



Cable Master Inc. 160 Pony Dr. #6A, Newmarket, ON, L3Y 7B6
905-715-7303 | Toll Free: 877-715-7303 | Fax: 905-715-7305 info@cablemasterinc.com